Description
The Victron SDFI0000000 Filax 2 is a transfer switch that moves sensitive AC loads, for example computers, industrial controls or modern entertainment gear, from one source to another. Mains, a generator or shore power usually serves as the priority source, and an inverter is typically the alternate. The switching time is less than 20 milliseconds, so sensitive equipment is designed to keep running without disruption.
Features
- Maximum current of 16 A.
- Open transition (break before make) design.
- Maximum load transfer time of 16 ms, and the same 16 ms for reverse transfer.
- Switches to the alternate source when the priority source voltage drops below its threshold or its frequency moves outside its limits.
- Reverse transfer to the priority source begins after it has stayed within the voltage and frequency limits for 30 seconds.
- Maximum continuous input voltage of 260 V.
- Not intended for high power household equipment such as washing machines or electric motors.
Specifications
The table below lists the Victron SDFI0000000 Filax 2 at a glance.
| Part number | SDFI0000000 |
| Brand | Victron |
| Revision | Rev: 1 |
| Maximum current | 16 A |
| Input voltage | 230 V AC |
| Input frequency | 50 Hz |
| Output voltage | 230 V AC |
| Output frequency | 50-60 Hz |
| Maximum continuous input voltage | 260 V |
| Maximum load transfer time | 16 ms |
| Reverse transfer time | 16 ms |
| Reverse switching delay | 30 seconds |
| Priority source low voltage switching threshold / reverse | 180 V / 188 V |
| Priority source low frequency switching threshold / reverse | 46 Hz / 52 Hz |
| Priority source high frequency switching threshold | 68 Hz |
| Priority source high frequency reverse switching threshold | 63 Hz |
| Operating temperature range | -20 to +50°C |
| Humidity | Max 95% (non condensing) |
| Dimensions (including terminals) | H120 x W255 x D75mm |
| Weight | 0.8 kg |