Description
The Victron Energy VM-3P5A is an energy meter that measures power and energy in single-phase, split-phase and three-phase AC systems. It is designed for standard 5 A current transformers, which are not included, so the measuring range can be matched to your system. It connects to a GX device, such as a Cerbo GX or Ekrano GX, through its Ethernet and VE.Can ports.
Features
- Measures power and energy in single-phase, split-phase and three-phase AC systems.
- Uses 5 A current transformers, which are not included.
- Can be set as a grid meter, PV inverter meter, generator meter or AC load meter.
- Configurable energy registration method: vector, arithmetic or absolute.
- Monitors electrical parameters, including line-to-neutral and line-to-line voltage and power factor.
- Plug and play as a grid meter; VictronConnect is needed to change the role or the current transformer primary rating.
- Status LED, which can be configured as an energy pulse output.
- Typical measurement points: distribution board, PV inverter, generator, inverter or inverter/charger, and grid meter in an ESS system.
Specifications
| Part number | REL200320100 |
| Model | VM-3P5A |
| Supported AC systems | Single-phase, split-phase and three-phase |
| Current connection | Via current transformers (not included) |
| Rated current | 5 A |
| Input voltage range, line to neutral | 85 to 265 V AC |
| Input voltage range, line to line | 150 to 460 V AC |
| Frequency | 50Hz or 60Hz, selectable |
| Consumption (W) | 1.85 W |
| Consumption (VA) | 3.5 VA |
| Refresh rate | 100 ms |
| Ethernet port | One RJ45 connector, Modbus UDP |
| VE.Can port | Two RJ45 connectors |
| Voltage connection terminal | Screw terminals 1,0 to 2,5 mm² (22 to 12 AWG) |
| Power type | Self-powered via N-L1-L2-L3 |
| Operating temperature range | -10 to 55 °C |
| Storage temperature range | -20 to 70 °C |
| Maximum humidity (non-condensing) | 90 % |
| Altitude | 2,000 m |
| Indoor or outdoor use | Indoor only |
What’s included
- VE.Can terminators
- Pluggable screw terminals for the current transformers
Not included: 5 A current transformers, which must be bought separately.
Fusing requirement
The VM-3P5A has no integrated fuse. External overcurrent protection must be installed at each of the four voltage measurement inputs: N, L1, L2 and L3, with a 500mA fuse at each input.